technical article
Smart Communicator Features
2012-2-1 10:17:53

: XDFD / Q Series Smart Communicator :

It is an instrument that can replace the operator and servo amplifier in the traditional DDD-type automation control system. Using system-on-chip technology, simple structure, superior performance, reliable quality, double digital plus light beam triple display

It is beautiful and eye-catching, and can be used with various domestic and foreign regulators or DCS control systems as a backup manual operation output unit for host failure and maintenance. This series of instruments are divided into: D type operation, Q welcome operation, hard hand operation.


The D-type hand-held actuator is operated by the control signal sent by the regulator or DCS and the valve position signal fed back by the actuator, and then directly outputs the positive and negative electrical signals to drive the electric actuator to control the positive and negative rotation of the motor.

Output the valve position signal to the regulator. When the operator automatically turns to manual, it outputs the status signal of the switching value to the regulator, which acts as a valve position tracking signal for the regulator.


输出线性电流或电压信号直接驱动气动阀,控制阀门的 The Q-type hand-held manipulator is operated by the regulator or DCS to send control signals and valve feedback signals from the actuator. The intelligent hand-held manipulator outputs a linear current or voltage signal to directly drive the pneumatic valve.

Switch and output valve position signal to regulator at the same time. When the operator automatically turns to manual, the state signal of the switch value is sent to the regulator, which serves as the valve position tracking signal.


The hard hand operation is an operator without automatic control. It only receives the valve signal and controls the output through human-machine dialogue. The output signal can be a positive and negative electrical signal (D-type hard hand operation) or a linear current and voltage signal. Fuck.

The valve opening position is determined by receiving the valve position signal and displaying the valve position.

Features

★ The input signal can be arbitrarily designated and selected.


★ The manual output value can be preset automatically or manually at startup.


★ Manual state auxiliary output.


★ Valve position feedback tracking output.


★ EM1 A manual function, the initial output value remains unchanged. After remote manual cancellation, it can remain manual or return to automatic state.


★ EM2-process manual function, initial value can be preset.


★ Valve position feedback error indication, valve Xian feedback disconnection can be automatically entered manual.


★ Tracking error error indication.


★ The control signal is automatically protected when the main input is disconnected and output to the motor, and the fault signal is output.


★ Two 16A bidirectional thyristors can be built in the meter to directly control the forward and reverse of the motor of the actuator.

★ All setting parameters can be stored for 10 years without losing.


★ The system resets automatically without crashing.


Technical index


★ Output signal: 4-20mA, 0-10mA


★ Regulator feedback input: 4-20mA, 0-10mA. 0-5V, 1-5V


★ Valve position feedback input: 0-10mA, 4-20mA, 0-5V, 1-5v


★ Valve position feedback output: 4-20mA, 0-10mA or 0-5V, 1-5VDC


★ Manual / Auto status output: off, automatic status; on, manual status.

★ Remote manual input of EM1: low level, which means that EM1 is valid

★ Remote manual input EM2: low level is valid: disconnection is invalid.


★ Power supply: 220VAC / 50Hz or 24VDC


从功能上分有纯手操和手自动手操两种类型,纯手操只与电动执行器相连接,通过面板开关按键直接控制执行机构的正、反转,具备手自动功能的 There are two types of intelligent manual operator: pure manual operator and manual automatic operator. Pure manual operator is only connected with electric actuators. It can directly control the forward and reverse of the actuator through the panel switch keys. It has the manual automatic function. of

The Communicator is installed between the actuator and the controller (regulator or computer-controlled DCS, PLC system). When the Communicator is in the manual state, the actuator is directly controlled by the Communicator. When in the automatic state, the actuator is controlled Right of hand

To the controller, the current and voltage signals from the controller are converted into switching signals or isolated control current and voltage signals to control the action of the electric actuator or electric valve positioner. From the control signal type, the communicator is divided into D type and

There are two types of Q-type. The D-type handheld programmer contains a servo amplifier. The forward and reverse of the DKJ and other series of electric actuators are controlled by manually pressing the keys on the panel. Control current

Electronic actuator or electric valve positioner of servo amplifier.


Second, the main features


The D-type handheld communicator contains a servo amplifier to directly drive the DKJ and other actuators controlled by the forward and reverse switch of the power supply. Q type can output isolated control current and voltage signals, and its high isolation of output current and voltage signals can guarantee

Control and stabilize the charged actuators. The valve position limit amplitude can be set to ensure that the actuator runs safely within the set safety valve position range. Valve position control action sensitivity can be set to prevent frequent movement of the actuator to ensure

Actuator life. With manual / automatic switching function, it is widely used in computer, regulator or DCS, PLC and other automatic control systems. With manual automatic status relay output. Valve position feedback signals can be current,

Voltage, variable resistance and other forms of input, suitable for all types of actuators.


Third, the main performance indicators


1. Display mode: The setpoint (SV) and feedback value (FB) are displayed by double-row four-digit LEDs, and the percentage of the setpoint and feedback value is displayed by double light beam simulation.


2. Display range: 0.0 to 100.0%, fixed to one decimal point.


3. Control and transmission output accuracy: ± 0.2% FS ± 1 character; ± 0.1% FS ± 1 character (special order required).

4. Input signal:


Valve position given input: 0 ~ 10mA, 4 ~ 20mA, 0 ~ 5V, 1 ~ 5V.


Valve position feedback input: 4 ~ 20mA.


5. Analog input impedance: current signal Ri = 100Ω; voltage signal Ri = 500KΩ.


6. Output load capacity:


Valve position feedback and then output signal: Ro≤500Ω at 4 ~ 20mA output; Ro≤1KΩ at 0 ~ 10mA output.


Q-type current load capacity: Ro≤500Ω at 4 ~ 20mA output; Ro≤1KΩ at 0 ~ 10mA output.


D-type load capacity: 30A / 220V, AC zero crossing trigger


7, alarm mode: 2 road lower limit alarm control, corresponding panel LED indication.


8. Remote control: remote hand / auto switch and alarm output, remote fault alarm, corresponding panel LED indication.


9.Alarm relay contact capacity: AC220V 3A or 24V 5A (resistive load).


10. Operating environment: Ambient temperature: -10 ~ 55 ℃, Ambient humidity: 10 ~ 90% RH.


11. Withstand voltage: input / output / power / communication ≥1000V.AC for 1 minute.


12. Insulation resistance: input / output / power / communication ≥100MΩ.


13. Power supply: AC 85 ~ 265V, frequency: 50Hz ± 2Hz;


DC power supply: DC 16V-32V


14. Power consumption: <4W