technical article
Faults and solutions of magnetic flap liquid level gauge
2011-8-18 10:10:06

First, the magnetic column level indicator 's flip column indication is abnormal
Cause: The magnetic flip column is demagnetized.
Remedy: Check the demagnetized part of the magnetic flip column, and then replace the demagnetized part
Leakage of the instrument of the magnetic flap level gauge
原因:检查密封处有没有密封好 1. Reason: Check if the seal is sealed properly

Exclusion method: compact the cover
原因:密封件损坏 2. Reason: Seal is damaged

Exclusion method: Replace the gasket
原因:焊缝开裂 3. Reason: Weld crack

Exclusion method: repair welding or send to the manufacturer for repair
3.Liquid level rise and fall without magnetic indicator
 
cause of issue:
 
浮子漏或者浮子损坏 1. The float is leaking or the float is damaged
 
浮子失磁 2. Float demagnetization
 
浮子室内有异物,浮子卡死或者不能升降 3. There is a foreign body in the float, the float is stuck or cannot be lifted.
 
Method of exclusion:
 
更换浮子 1. Replace the float

清理液位计的测量桶 2.Clean the measuring barrel of the level gauge